BENEFIT
Each of our surge arrester is manufactured with the utmost care and undergoes rigorous testing according to accreditation standards.
echnical Specifications
YH5W surge arresters has been verified to meet Station Class requirements of IEEE C62.11 (IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits) and Line Discharge Class 3 requirements of IEC 60099-4 (IEC Standard for Metal-Oxide Surge Arresters without gaps for AC Systems). The YH5W surge arrester is designed to meet the following technical specifications:
Polymer housing color |
Sky blue |
|
Rated voltage (kVrms) |
0.28 ~ 54 |
|
Continuous operating voltage (COV) (kVrms) |
0.24 ~43.2 |
|
Max. residual voltage at nominal discharge current (kVrms) |
1.3 ~135 |
|
Min. reference voltage at 1mA d.c. (kVrms) |
0.6 ~ 76 |
|
|
15 ~ 20 |
|
|
60 ~120 |
|
Discharge current withstand strength
|
Low current 2 ms rectangular wave(Apeak) |
50 ~ 400 |
|
10 ~ 65 |
Services Conditions
Design altitude |
2,000 m |
Ambient temperature |
|
Frequency |
48 Hz to 62 Hz |
Allowed seismic intensity |
Less than 7 |
Max. wind speed |
35 m/s |
Max. pollution severity |
IV |