BENEFIT
Each of our surge arrester is manufactured with the utmost care and undergoes rigorous testing according to accreditation standards.
HY5CX liner surge arresters have a fixed spark gap between two spherical electrodes; the spark gap is placed in series that galvanically isolates the active part of the arrester from the line voltage in normal conditions. In case of lightning, the spark gap is ignited and the overvoltage is safely discharged to the ground. In preventing all insulator flashovers by lightning strikes, YH5CX line surge arresters increase network stability as well as the availability of the overhead line.
In normal operating conditions, because the series gap disconnects the MOV blocks from the system voltage, there is no leakage current, thus extending the life of the arrester.
Unique and patented design offers other benefits such as easy installation, repelling birds and snow accumulation, and prevention of slippage.
Polymer housing color |
Sky blue |
|
System rated voltage (kVrms) |
10 |
|
Rated voltage of arrester(kVrms) |
12.7 and 13 |
|
Min. power-frequency withstand voltage(kVrms) |
26 |
|
Min. reference voltage at 1mA d.c. (kVrms) |
19 |
|
Max. lightning impulse residual voltage (Vpeak) |
36 and 40 |
|
|
100 |
|
Discharge current withstand strength
|
Low current 2 ms rectangular wave(Apeak) |
150 |
|
65 |
|
Series gap distance (mm) |
40 |